Understanding the WatchMon - Control Logic - TempView

Administrative screen for the WatchMon supervisor hardware providing a summary, and how to understand and see the various fields available to configure the Temperature aspect of control logic.

Field Definitions


Live Readings: values read from device.

Critical High (CT9):  Cell temperature threshold that is OK to operate, if above will change state when monitoring is enabled, output is connected to the Critical Contactor.

CMU Alert High (CT8): Cell temperature warning when above will flash RED led on CellMon.

Discharge High (CT7):   Cell temperature threshold that is OK to operate, if above will stop the discharging state when monitoring is enabled.

Charge High (CT6): Cell temperature threshold that is OK to operate, if above will stop the charging when monitoring is enabled.

Cool (CT5): Cell temperature threshold that is OK to operate, if above will start the cooling control when monitoring is enabled.

Heat (CT4):  Cell temperature threshold that is OK to operate, if below will start the heating control when monitoring is enabled.

Charge Low (CT3):  Cell temperature threshold that is OK to operate charging, if below will stop the charging when monitoring is enabled.

Discharge Low (CT2):  Cell temperature threshold that is OK to operate, if below will stop the discharging state when monitoring is enabled.

Critical Low (CT1):  Cell temperature threshold that is OK to operate, if below will change state when monitoring is enabled, output is connected to the Critical Contactor.

Thermal Readings - Ambient
Live Readings 

Critical High (BT9):  WatchMon supervisor temperature threshold that is OK to operate, if above will change state when monitoring is enabled, output is connected to the Critical Contactor.

Discharge High (BT7):   WatchMon supervisor temperature threshold that is OK to operate, if above will stop the discharging state when monitoring is enabled.

Charge High (BT6):  WatchMon supervisor temperature threshold that is OK to operate, if above will stop the charging when monitoring is enabled.

Cool (BT5):  WatchMon supervisor temperature threshold that is OK to operate, if above will start the cooling control when monitoring is enabled.

Heat (BT4):  WatchMon supervisor temperature threshold that is OK to operate, if below will start the heating control when monitoring is enabled.

Charge Low (BT3): WatchMon supervisor temperature threshold that is OK to operate, if below will stop the charging when monitoring is enabled.

Discharge Low (BT2):  WatchMon supervisor temperature threshold that is OK to operate, if below will stop the discharging state when monitoring is enabled.

Critical Low (BT1):  WatchMon supervisor temperature threshold that is OK to operate, if below will change state when monitoring is enabled, output is connected to the Critical Contactor.

Link to this help screen.

Troubleshooting

If figures shown on this page need changing please go to the following links to change the designated items.

Hardware Cellmon:  CT8

Logic Critical Battery OK: CT1, CT9, BT1, BT9

Logic Charging: CT3, CT6, BT3, BT6

Logic Discharging:  CT2, CT7, BT2, BT7

Logic Thermal:  CT4, CT5, BT4, BT5

Did this answer your question? Thanks for the feedback There was a problem submitting your feedback. Please try again later.

Still need help? Contact Us Contact Us