How to control a Eltek Flatpack2 with WatchMon
CAUTION: Not recommended for new projects, provided for legacy project support
Here are the steps to configure the Eltek Flatpack2 2000W 48V HE Power Supply/Rectifier to the WatchMon supervisor.
CAUTION: Example shown is for a demo LiFePO4 cell pack 16S1P, ensure that you adopt suitable values to your application and comply with the battery suppliers recommendation.
Step 1 - Install communication cable to charger via CAN port on WatchMon.
For newer WatchMon (note 120 Ohm resistor shares CANbus High and CANbus Low
For older WatchMon with 4 pin CAN see below
Step 2 - Initial rear view of Eltek Flatpack2 without connector socket
Step 3 - Install canbus communication cable with twisted (~10 per 10cm)
Step 4 - Install AC power plug
Step 5 - Install Anderson DC battery plug
Step 6 - Install 120 canbus terminating resistor
Step 7 - On bottom pcb cover the resistor and terminal pins with hot glue
Hot glue does not substitute appropriate insulation below this pcb.
Step 8 - Finished assembly
NB: Rectifier should have additional enclosure added to meet relevant compliance.
Step 9 - Navigate to Hardware and then Integration tab.
Step 10 - Select Canbus protocol to "Eltek FlatPack2 HE2000/48" and Save.
Step 11 - Navigate to Control Logic, then Charging tab.
Step 12 - Adjust the charging control logic to suit the application.
Notes:
- Limited power must be enabled.
- Cell Hi Cutout should be above the CellMon bypass voltage threshold as a safe guard target.
- Low power current should suit the bypass capability of CellMon.
- When the bypass current is above Initial will trigger the system to low power.
- When the bypass current for all cellmons is above Final the system will complete charging cycle.
Step 13 - Navigate to Hardware, then CellMon tab.
Step 14 - Adjust the CellMon bypass voltage to suit the application.
Note: Make sure to "Device Sync" the changes to the CellMons.
Step 15 - Navigate to the Remote tab on the Control Logic screen.
Step 16 - Adjust the remote charging target to suit the application.
Notes:
- Scaling must be 100 for voltage.
- Scaling must be 100 for current.
- Low power must be enabled on charging tab.
- Low power current should suit the bypass capability of CellMon.
- Charger voltage target needs to be sufficient for all cells to reach bypass threshold.
- Maximum charging rate of rectifier is 42A
Step 17 - Navigate to Telemetry, then Live Stats to observe system operation.
Notes:
- Scaling must be 100 for voltage.
- Scaling must be 10 for current.
- Do not run low power mode on discharging tab.
- Control logic discharge voltage cutout should match the remote target.
Step 18 - Navigate to Control, then Remote to observe inverter info received
Notes:
- Charge Target Voltage - voltage cutout sent to inverter when charging
- Charge Target Current - ampere limit sent to inverter when charging
- Charge Actual Flags - reported charging mode and operating state flag received from inverter
- Charge Actual Voltage - charging cutout volatge setpoint sent from inverter
- Charge Actual Current - reported battery amperes from inverter when charging
- Charge Actual Power - reported battery state of charge SoC% received from inverter
- Charge Actual Temperature - reported battery temperature from inverter
- Discharge Target Voltage - voltage cutout sent to inverter when discharging
- Discharge Target Current - ampere limit sent to inverter when discharging
- Discharge Actual Flags - reported active message error flag received from inverter
- Discharge Actual Voltage - reported battery voltage from inverter
- Discharge Actual Current - reported battery amperes from inverter when discharging
- Discharge Actual Power - reported relay state flag received from inverter
- Discharge Actual Temperature - not used