How to control a Redback hybrid SH5000 inverter/charger with a WatchMon
Here are the steps to configure the Redback smart hybrid SH5000 inverter/charger to the WatchMon supervisor.
CAUTION: Example below has values shown for a demo LiFePO4 cell pack, ensure that you adopt values suitable to your application and comply with the battery suppliers recommendation.
Step 1 - Install communication cable to charger via CAN1 port on WatchMon.
For newer WatchMon (note 120 Ohm resistor shares CANbus High and CANbus Low
For older WatchMon with 4 pin CAN see below
Step 2 - Install communication cable to Reback BMS socket (extract from manual)
Typical Cat 5 cable colour pin combination.
Redback RJ45 pin 7 (typically Brown/White)connects to Can-H WatchMon
Redback RJ45 pin 8 (typically Brown) connects to Can-L WatchMon
Redback RJ45 pin 1 (typically Orange/Green)connects to WatchMon GND
NB: Using a CAT5 ethernet cable strip back the cable and connect to pins identified above.
Step 3 - Navigate to Hardware, then Integration tab.
Step 4 - Select Canbus protocol to "Redback Hybrid SH5000" and Save.
Step 5 - Navigate to Control Logic, then Charging tab.
Step 6 - Adjust the charging control logic to suit the application.
Notes:
- Low power must be enabled.
- Cell Hi Cutout should be above the CellMon bypass voltage threshold as a safe guard target.
- Low power current should suit the bypass capability of CellMon.
- When the bypass current is above Initial will trigger the system to low power.
- When the bypass current for all cellmons is above Final the system will complete charging cycle.
Step 7 - Navigate to Hardware, then CellMon tab.
Step 8 - Adjust the CellMon bypass voltage to suit the application.
Note: Make sure to "Device Sync" the changes to the CellMons.
Step 9 - Navigate to the Remote tab on the Control Logic screen.
Step 10 - Adjust the remote charging target to suit the application.
Notes:
- Scaling must be 10 for both voltage and current.
- Low power must be enabled on charging tab.
- Low power current should suit the bypass capability of CellMon.
- Charger voltage target needs to be sufficient for all cells to reach bypass threshold.
Step 11 - Adjust the remote discharging targets to suit the application.
Notes:
- Scaling must be 10 for both voltage and current.
- Do not run low power mode on discharging tab.
- Control logic discharge voltage cutout should match the remote target.
Step 12 - Navigate to Telemetry, then Live Stats to observe system operation.